- 3.9W + 0.03 W/mA * (current draw from the auxiliary output source including analog outputs)
PCM-1 REV E (obsolete):
- 3.07W + 0.03 W/mA * (current draw from the auxiliary output source including analog outputs)
AIN-1:
- 3.9W + 0.03 W/mA * (current draw from the auxiliary output).
ASM-1:
- 2.5W
DIN-1:
- 1.3W + 0.03 W/mA * (current draw from the auxiliary output source)
DAM-1 or 2 (ISO or BK):
- 1.3W + 0.03 W/mA * (current draw from the auxiliary output source) + 0.05W/relay * (number of relays being used)
DAM-3:
- 1.5W + 0.03 W/mA * (current draw from the auxiliary output source) + 0.07W/relay * (number of relays being used)
NIM-1, NIM-3, or NIM-4:
- 2.8W
NIM-2:
- 4.67W + 0.24W/copper-port * (number of copper ports) + 1.37W/Fiber-port * (number of Fiber-Optic Ports) + 0.8W/Fail-over * (1 for Fail-over Relay Option, 0 otherwise)
NIM-6:
- 3W
NIM-7:
- 4W
UCM-1, UCM-2, UCM-2AMI, or UCM-2SVI:
...
Note2: There is a reduction of allowable output power for the DCP-1 that varies with input temperature voltage / maximum ambient operating temperature / and EMI filters on the wiring hub. At 65C maximum operating temperature and EMI filters on the DCP-1 wiring hub, the following input voltage vs. maximum output power should be used:
...