Version Details
Release Date: 8/11/2011
Version: v1.1
Download Links
ASM_DefaultSchema.zip (56 kB)
Download Contents
This zip files contains the HWI and schemas associated with the default ASM-1 schema. It provide all of the typical functionality that is normally associated with an alarm notification and acknowledge appliance.
Installation Instructions
Create a folder and unzip all of the files into that folder. Open ASM-1.hwi in Design Pad v4.5.230 or higher.
General Overview of Functionality
Setup
In the HWI Module Variable Settings screen, set bChannelxEnabled (where x is 1 to 10) to true to indicate the associated alarm input channel is active; set to false to deactivate the associated alarm input channel.
Operation
Each active channel will be monitored by the ASM-1 module to be in one of the following states:
...
- Normal: Channel monitoring is enabled
- Cutout: Channel monitoring is disabled (i.e. associated process is down for maintenance, etc.) The 'State' LED is deactivated when a channel is disabled.
- Standby: Channel monitoring is enabled and the last Alarm Active or Wiring Fault condition was acknowledged
User Interface
- Press the up and down arrows 'SEL. NEXT' (down arrow) and 'SEL. PREV' (up arrow) buttons to select the channel to operate on. The 'Select' column of LEDs will show the current channel selected by illuminating the associated LED.
- Press the 'ModeMODE' button to change the selected channel between Normal to Cutout, Cutout to Normal, or from Standby to Cutout.
- Press the 'AckACK' key for less then 5 seconds to acknowledge the condition on the currently selected channel. If the channel is in alarm, the mode of the channel will transition to Standby when acknowledged.
- Press the 'AckACK' key for more then 5 seconds to acknowledge the condition on all channels.
- Press the 'TestTEST' button to perform a lamp test.