NIM-7 Interpreting the System Status and Network Activity Lights
If the NIM-7 is configured for Slave Mode, interpret the LEDs as follows:
System Status LED
1Hz Red == NIM-7 PROFIBUS co-processor is waiting to load firmware
5Hz Red == NIM-7 PROFIBUS co-processor is downloading firmware
Other Red Flash == NIM-7 PROFIBUS co-processor hardware error detected
Green == Cyclic data exchange in progress
5Hz Green == No cyclic data exchange
Other Green == Faulty configuration or waiting for NIM-7 main processor to respond
Off == No schema / network configuration loaded or no power
Network Activity LED
Green == Configured and exchanging data with a master
Red == Application program not synchronous with the network
Off == Slave has not reached the data exchange state yet
If the NIM-7 is configured for Master Mode, interpret the LEDs as follows:
System Status LED
1Hz Red == NIM-7 PROFIBUS co-processor is waiting to load firmware
5Hz Red == NIM-7 PROFIBUS co-processor is downloading firmware
Other Red Flash == NIM-7 PROFIBUS co-processor hardware error detected
Green == Cyclic data exchange with at least one slave in progress
5Hz Green == Ready for data exchange, no connection to any slaves
Other Green == Faulty configuration or waiting for NIM-7 main processor to respond
Off == No schema / network configuration loaded or no power
Network Activity LED
Green == Master has the token and is functioning
Flashing Green == Master is sharing the token with other masters on network
Red == Cannot communicate with one or more slaves or short circuit on wiring detected
Off == Not configured or cannot obtain token for network