Shielded CAT-5E (for example LSC50SW-4 or M24643/59-04UO) is adequate to wire the most signals between the two segments as follows:
...
For the last two signals, GND and +25.5V, the wiring requirements vary with cable length between the two UCM-2NB modules . Shorter segments, under 5 feet, and power used by the node. Segments under 5 feet and with a 25W or less power draw (i.e. less than two non-redundant supplies) can use shielded CAT-5E cable. Longer segments, Segments between 5 feet and 10 feet , or nodes requiring greater then 25W of power (i.e. two or more non-redundant supplies) should use 16 AWG stranded wire in a shielded cable.