The UCM-2_NB is used to split a Chameleon Node into two physically separate segments but keeps them electrically and logically a single node.

The distance between the two UCM-2_NB modules is limited by backplane signal quality and the cable length should be 10 feet or less. It is recommended that a Backplane Termination cable Assembly, FA P/N: 01020-150, be installed at the logical ends of each node (i.e. the physical ends that are not the UCM-2BN modules).

Shielded CAT-5E (for example LSC50SW-4 or M24643/59-04UO) is adequate to wire the most signals between the two segments as follows:

  • Connect BP-1 to BP-10 (terminal numbers 13-17 and 19-23) to the terminal of the same name/number in the partner UCM-2NB.
  • The signals BP-3 and BP-8 (terminal numbers 15 and 21) should be connected using one twisted pair of the CAT-5E cable.

For the last two signals, GND and +25.5V, the wiring requirements vary with cable length between the two UCM-2NB modules. Shorter segments, under 5 feet, can use shielded CAT-5E cable. Longer segments, between 5 feet and 10 feet, should use 16 AWG stranded wire in a shielded cable.