4.6.14

4.6.14 Software Release Notes

Document Number: PDG-RN-2013-001
Internal Release Date

May 17th, 2013

External Release Date

November 5th, 2013

NEW FEATURES AND CHANGES

New Features

  • Support for the DAM3 module.  (PR: DAM-3, SWCHA-671, SWDPGIV-500, SWDPGIV-509)
  • Ability to program Chameleon nodes with NIM2 in slave position.  (SWDPGIV-482)
  • Ability to upgrade firmware over IR without removal of NIM2.  (SWDPGIV-481)
  • New toolbar button for querying hardware.  (SWDPGIV-480, SWDPGIV-495)
  • Ability to program node using node.run file.  (SWDPGIV-498, SWDPGIV-514)
  • Ability to sort on multicast and initial value columns.  (SWDPGIV-490)
  • Added new 16 bit bytewise checksum field for binary communications channel.  (SWCHA-677)

Changes

Chameleon - General
  • Added support for DAM3 solid state relay module.  (PR: DAM-3, SWCHA-671, SWDPGIV-500)
  • Corrected issue where right side power supply error would not clear when cause was corrected.  (SWCHA-657)
  • Corrected issue which could result in load of quad decoder not outputting the values loaded.  (SWCHA-669)
  • Report error on ARM boards if serial number is not set.  (SWCHA-672)
  • Updated crash dump code.  (SWCHA-674)
  • Increased retries/delay if flash write fails to complete in expected time.  (SWCHA-678)
  • Altered firmware upgrade timing to improve process when multiple modules of same type are in node (SWCHA-645)
  • Improved interrupt handling for IRDA comm channel to reduce "Can't send message" errors.  (SWCHA-686)
  • Added extra check of flash write completion before rebooting when upgrading firmware.  (SWCHA-685)
  • Added check to avoid crash under low memory conditions when receiving large fairnet message.  (SWCHA-679)
  • Improved firmware upgrade process by utilizing memory stream for initial image download.  (SWCHA-678, SWCHA-689)
Design Pad and Schema Viewer
  • Corrected issue where a moved/copied workspace was not detected properly.  (SWDPGIV-422)
  • Corrected issue where unconnected local output variable in subschema could cause crash.  (SWDPGIV-441)
  • Corrected issue that would lock up Design Pad when updating multiple NIM2s.  (SWDPGIV-463)
  • Report error if opening workspace with incorrect under current/over current settings.  (SWDPGIV-467)  See PDG-TR-2013-002.pdf for details.
  • Corrected issue where negative Y label offset could cause crash.  (SWDPGIV-478)
  • Improved AVN1 menu handling.  (SWDPGIV-483,485,489)
  • Corrected crash when a float and a boolean variable had the same name.  (SWDPGIV-488)
  • Corrected issue which could cause a crash in a subschema with variables in the same subschema with the same name and different scopes.  (SWDPGIV-491)
  • Corrected issue with edit dialog on ramp profile operator which prevented editing ramp.  (SWDPGIV-492)
  • Corrected display issue when HWI window was scrolled and incorrect module could be selected.  (SWDPGIV-493)
  • Correct typo in warning dialog message.  (SWDPGIV-501)
  • Added delay to firmware upgrade to prevent errors that could be reported with certain node configurations.  (SWDPGIV-503)
  • Corrected an issue where clicking on step on an hwi could result in Design Pad crash.  (SWDPGIV-505)
  • Added AVN-1 context menus(SWDPGIV-489)
  • Treat boards missing hardware information as having new flash.  (SWDPGIV-511)
Smart Valve
  • Added code to process custom properties from Design Pad during motor actuation.  (SWSV-266)
  • Corrected issue where phase error detected during first 30 seconds would not clear if not resolved until after 30 seconds.  (SWSV-269)
  • Corrected issue with position sensor communication error being reported during idle.  (SWSV-270)
NIM-2
  • Corrected small memory leak in NIM2 that could occur in limited circumstances.  (SWCHA-667)
  • Correct issues with temperature sensor readings.  (SWCHA-676)
AIN-1
  • Support added for rev C or rev D boards missing calibration files.  (SWCHA-621)
FAC-2100
  • Corrected issue with fatt files reported to customers during normal firmware upgrades.  (SWFACGII-83)

DOWNLOAD LINKS

Design Pad G4

Download link

md5 checksum

Description

DesignPadG4_Release_v4.6.14.zipb5000db1f2529af762b336d3aa64cc51

Windows software installation files

Design Pad G4 Release Package

This file contains the Fairmount Automation v4.6.14 software release. It includes software for the following products:

  • Design Pad G4
  • Schema Viewer G4
  • FANDA Tools (SDK, Browser, OPC Server)
  • FairNET OPC Server
  • Firmware for:
    • All Chameleon Modules (SEE SPECIAL CONSIDERATIONS SECTION BELOW)
    • FAC-2100
    • Smart Valve

Schema Viewer G4

Download link

md5 checksum

Description

SchemaViewerG4_Release_v4.6.14.zip

b5ed4bd1345b4e823645bd8271aa45ee

Schema Viewer G4

Schema Viewer G4 Release Package

This file contains the Fairmount Automation v4.6.14 software release. It includes software for the following products:

  • Schema Viewer G4
  • Firmware for:
    • All Chameleon Modules (SEE SPECIAL CONSIDERATIONS SECTION BELOW)
    • FAC-2100
    • Smart Valve

Fairmount Device Firmware

It is NOT necessary to download these file separately as they are included in the Design Pad and/or Schema Viewer v4.6.10 installation. They can be found in \Program Files\Fairmount Automation\<PROGRAM NAME> folder (where <PROGRAM NAME> is 'Design Pad G4' or 'Schema Viewer G4').

Download link

md5 checksum

Description

Chameleon.4.6.14.$cc

66724d0e43a73e5cf06a687759506ddc

Firmware for all modules except NIM-2

NIM2L.4.6.14.$cc

dcf8a4791f3853db779208932e57ae4a

Firmware for NIM-2

FAC_2100.4.6.14.$cc

dbeb3c82951c35d85a27ca7a46a49e24

Firmware for FAC-2100 regular and enhanced

Smartvalve.4.6.14.$cc

5303653b9b646ef6131925ec2cb052e9

Firmware for Smart Valve

NIM2.4.5.230_downgrader.bin

99630b095af5f184c09e592d48f87846Firmware to downgrade NIM2 4.5.264+ to 4.5.230

SPECIAL CONSIDERATIONS

  1. As always, customers should ensure the updated software meets their requirements in a test environment prior to deploying in a production environment.
  2. Power should not be removed during the firmware update process or the device may need to be returned to the factory.
  3. If you are upgrading from a release prior to 4.5.264, you must review the release notes for 4.5.264_Patch 2.  There are several important considerations when upgrading from pre-4.5.264 releases to release 4.6 that are included in that document..

    IMPORTANT :  This especially impacts the NIM2 firmware when upgrading from older releases as the NIM-2 operating system changes and there are additional actions that must be performed when compared to a standard firmware update. As such, the process to update the first firmware upgrade from a version prior to 4.5.264(Patch 2) on the NIM2 can take up to 10 minutes. The status LED can be steady or flashing green, amber and/or RED during that time. The board must not be removed from the node or power cycled during that time. Failure to follow this guideline will likely result in a nonfunctional board. This additional time for the firmware update is only needed for NIM-2 modules.

INSTALLATION

Installing Design Pad G4

This patch will overwrite any previous installation. If you need to keep those older versions you may manually rename the existing \Program Files\Fairmount Automation\Design Pad G4 folder to a custom name. Run the FADP.exe file in those folders to execute the previous version.

Follow these steps to install Design Pad G4:

  1. Transfer the G4 Software ZIP file to the local computer.
  2. UnZIP the file into a temporary folder on the local computer.
  3. Navigate to the temporary folder and open the 'Design-Pad-Installer' subdirectory.
  4. Run setup.exe and follow the prompts.
  5. Design Pad G4 will not function without a valid license.
    1. Any existing Design Pad G4 or G3 license will work with this patch update.
    2. If you do not have an existing license then, after installation is complete, follow the on-screen instructions to send the license request to Fairmount Automation. After you receive the license file, copy it into your "\Windows" or "\Program Files\Fairmount Automation\Design Pad G4" folder.

Installing Schema Viewer G4

This patch will overwrite any previous installation. If you need to keep those older versions you may manually rename the existing \Program Files\Fairmount Automation\Schema Viewer G4 folder to a custom name. Run the FADP.exe file in those folders to execute the previous version.

Follow these steps to install Schema Viewer G4:

  1. Transfer the G4 Software ZIP file to the local computer.
  2. UnZIP the file into a temporary folder on the local computer.
  3. Navigate to the temporary folder and open the 'Schema-Viewer-Installer' sub-directory.
  4. Run setup.exe and follow the prompts.
  5. Schema Viewer G4 will not function without a valid license.
    1. Any existing Schema Viewer G4 or G3 license will work with this patch update.
    2. If you do not have an existing license then, after installation is complete, follow the on-screen instructions to send the license request to Fairmount Automation. After you receive the license file, copy it into your "\Windows" or "\Program Files\Fairmount Automation\Design Pad G4" folder.

Chameleon Installation

IMPORTANT:  When updating nodes that contain NIM-2 modules, the NIM-2s should be updated first and then the non-NIM-2 modules. This will ensure that the NIM-2s maintain the needed network settings to perform the update over Ethernet.

Updating NIM-2 Modules:

Ensure the NIM-2(s) are configured (IP address loaded, etc.) to be on the same network as the computer that is performing the update.

  1. Start Design Pad or Schema Viewer v4.6.14 or higher.
  2. Select 'Use Ethernet' from the Communications Menu.

To Update a Single NIM-2 from Design Pad G4 or Schema Viewer G4 v4.6.14:

    1. Open the Workspace and HWI associated with the NIM-2 to update.
    2. Choose 'Firmware Update' from the Communications Menu
    3. When prompted, select the NIM2L.4.6.14.$cc file
    4. Follow the on-screen instructions to complete the download

To Update Multiple NIM-2s from Design Pad G4 or Schema Viewer G4 v4.6.14:

    1. Open the Workspace associated with the NIM-2 to update.
    2. Right-click on the word 'Workspace' in the Workspace window and select Update Firmware (All Ethernet Hardware) from the Communications sub-menu.
    3. Press the 'Browse' button and select the NIM2L.4.6.14.$cc file
    4. Select the NIM-2s to update in the 'Select Ethernet Hardware' window.
    5. Press the 'Upload' button to start the update process.

Updating Non-NIM-2 Modules:

  1. Start Design Pad or Schema Viewer
  2. Choose 'Firmware Update' from the Communications Menu
  3. Align the IR wand to the right-most module
  4. Select the Chameleon.4.6.14.$cc file when requested
  5. Follow the on-screen instructions to complete the download 

FAC-2100 Installation

  1. Start Design Pad or Schema Viewer
  2. Attach the serial cable from the computer to the COM1 port on the controller
  3. Choose 'Firmware Update' from the Communications Menu
  4. Select the FAC_2100.4.6.14.$cc file when requested
  5. Follow the on-screen instructions to complete the download

Smart Valve Installation

Due to the time needed to perform an IR update, it is recommended that the firmware update be done whenever possible using the Ethernet interface (a few minutes) rather than the serial IR interface (40+ minutes).

Updating Smart Valves using Ethernet:

  1. Ensure the Smart Valve(s) are configured (IP address loaded, etc.) to be on the same network as the computer that is performing the update.
  2. Start Design Pad or Schema Viewer 4.6.14 or higher.
  3. Select 'Use Ethernet' from the Communications Menu.

To Update a Single Smart Valve:

    1. Open the Workspace and HWI associated with the Smart Valve to update.
    2. Choose 'Firmware Update' from the Communications Menu
    3. Press the 'Browse' button and select the Smartvalve.4.6.14.$cc file
    4. Keep 'Preserve network settings after reboot' checked.
      1. Press the Upload button to start the update process.

To Update Multiple Smart Valves:

    1. Open the Workspace associated with the Smart Valves to update.
    2. Right-click on the word 'Workspace' in the Workspace window and select Update Firmware (All Ethernet Hardware) from the Communications sub-menu.
    3. Press the 'Browse' button and select the Smartvalve.4.6.14.$cc file
    4. Select the Smart Valves to update in the 'Select Ethernet Hardware' window.
    5. Keep 'Preserve network settings after reboot' checked.
    6. Press the 'Upload' button to start the update process.

During the firmware update process, any existing Smart Valve program will be erased. If desired, reprogram valve by opening the desired program and selecting Program Hardware (reset schemas) from the Communications Menu.

Updating the Smart Valves using IR:

  1. Start Design Pad or Schema Viewer
  2. Open the Workspace and HWI associated with the Smart Valve to update.
  3. Choose 'Firmware Update' from the Communications Menu
  4. Remove the IR blocking plug (if installed) and align the IR wand to the actuator
  5. Select the Smartvalve.4.6.14.$cc file when requested
  6. Follow the on-screen instructions to complete the download

During the firmware update process, any existing Smart Valve program will be erased. If desired, reprogram valve by opening the desired program and selecting Program Hardware (reset schemas) from the Communications Menu.