Power

Typical Power Draw

The following table shows the typical power draw (in Watts) for the FAC-2100 under various conditions:

Test Condition

18VDC Power

24VDC Power

28VDC Power

36VDC Power

Unit On, Idle (No Schema)

4.2

4.4

4.7

5.7

Additional Power for All
Front Panel LED On

2.8

2.8

2.8

2.8

Additional Power for Analog
and Digital Outputs On

0.25

0.25

0.25

0.25

Additional Power for
3 Solid State Relays and
2 Mechanical Relays

1.3

1.3

1.3

1.3

Additional Power per mA
of Load on 28V Auxiliary Output

0.05

0.05

0.05

0.05

Power Connection Diagram

The diagram below shows the connections for powering the device. Note that a chassis ground braid must be connected between the stud on the back of the device and an Earth/chassis grounding point to provide EMI and ESD protection. The braid used during MIL-STD 461 EMI testing can be ordered using Fairmount Automation Part Number: 30110-015.


Unknown macro: {scroll-align-center}


Wiring the FAC-2100's DC Input Power


Warning: An improperly grounded case could result in electrical shock or incorrect operation of the controller.

Fuses

Each FAC-2100 has a fuse located in the rear of the device on the connector panel. Refer to the [Parts List] section for the fuse specification and ordering information.

Auxiliary Output Power

The FAC-2100 contains a 28V isolated (from the DC input power source) output source available to power sensors, actuators, etc. Most circular connectors on the back of the FAC-2100 contain pins that provide access to this source.


Note that the design of the Auxiliary Output Power source allows for multiple FAC-2100s to short together (no steering diodes are required) their power sources to provide a redundant source. As an example, this feature can be useful when multiple controllers are reading the same powered sensor – by connecting the Auxiliary Output Power from all controllers to the sensor it ensures that all controllers will be able to read the sensor if any or all others are offline.