Mechanical Installation (FAC2100)
Mechanical Installation
Panel / Console Cutout
The FAC-2100 is designed for installation in a panel or console between 1/16 and 1/2 inch thick. The figure below shows the required panel cutout dimensions.
Cutout Required to Install the Controller
IMPORTANT NOTE: The mounting holes must not exceed 0.312" in diameter (the recommended mounting hole diameter is 0.281".)
Â
Mechanical Assembly
After cutting out the pattern shown above, place the mounting assembly on the mounting plate in the following order:
Â
- Silicone Locking Clamp Gasket
- FAC-2100 controller body
- Silicone Bezel Gasket
- Four Mounting Spacers
- Steel Bezel
Â
The Silicone | The Silicone |
The Steel | The Steel Bezel |
From the rear of the mounting plate, slide the locking clamp over body of the controller with the PEM nuts facing away from the mounting plate. While holding the locking clamp, insert the four 10-32 hex socket head cap screws into each hole of the bezel and tighten with a 5/32 hex head wrench. The recommended seating torque for the 10-32 hex socket head screws is 76 in-lbs.
Mounting Configuration
Â
Dimensions
If the FAC-2100 contains miniature cylindrical connectors, the mounting depth of the controller behind the mounting panel/plate (measured from the front face of the mounting panel/plate to the ends of the miniature cylindrical connector receptacles and fuse holder(s)) is 7.2 inches. When strain-relieving plugs are attached to the connector receptacles (not including the depth associated with wire exiting the plugs), the mounting depth required is 8.5 inches.
The controller will extend 0.56 inches in front of the mounting plate (measured from the front face of the mounting panel/plate to the heads on the four 10/32 x 1/4 mounting bolts).
Case Size
Â