Mechanical Installation (FAC2100)

Mechanical Installation

Panel / Console Cutout

The FAC-2100 is designed for installation in a panel or console between 1/16 and 1/2 inch thick. The figure below shows the required panel cutout dimensions.

Cutout Required to Install the Controller


IMPORTANT NOTE: The mounting holes must not exceed 0.312" in diameter (the recommended mounting hole diameter is 0.281".)

 

Mechanical Assembly

After cutting out the pattern shown above, place the mounting assembly on the mounting plate in the following order:

 

  1. Silicone Locking Clamp Gasket
  2. FAC-2100 controller body
  3. Silicone Bezel Gasket
  4. Four Mounting Spacers
  5. Steel Bezel

 

The Silicone
Locking Clamp
Gasket

The Silicone
Bezel Gasket

The Steel
Locking Clamp

The Steel Bezel


From the rear of the mounting plate, slide the locking clamp over body of the controller with the PEM nuts facing away from the mounting plate. While holding the locking clamp, insert the four 10-32 hex socket head cap screws into each hole of the bezel and tighten with a 5/32 hex head wrench. The recommended seating torque for the 10-32 hex socket head screws is 76 in-lbs.

Mounting Configuration

 

Dimensions

If the FAC-2100 contains miniature cylindrical connectors, the mounting depth of the controller behind the mounting panel/plate (measured from the front face of the mounting panel/plate to the ends of the miniature cylindrical connector receptacles and fuse holder(s)) is 7.2 inches. When strain-relieving plugs are attached to the connector receptacles (not including the depth associated with wire exiting the plugs), the mounting depth required is 8.5 inches.


The controller will extend 0.56 inches in front of the mounting plate (measured from the front face of the mounting panel/plate to the heads on the four 10/32 x 1/4 mounting bolts).

Case Size

Â